RA Series EcoTouch® Insulation are lightweight blankets. Designed to provide excellent dimensional stability, excellent thermal and acoustical performance, and easy handling and installation. Great for Water Heater, HVAC double Wall, Sound Panel, and other OEM applications.

Performance Attributes

Acoustic Performance icon

Acoustic Performance

Easy Installation icon

Easy Installation

Thermal Comfort icon

Thermal Comfort

Technical Information

Physical Properties

Property

Test Method

Value

Surface Burning Characteristics1

ASTM E84 or UL723Meeting 25/50
Operating TemperatureASTM C411Up to 450ºF (176ºC)
CorrosionASTM C665Meets standard
Mold GrowthASTM C1338Meets standard
Thermal ConductivityASTM C518See table
Sound AbsorptionASTM C423See table
1. The surface burning characteristics of these products have been determined in accordance with UL723, ASTM E84, or CAN/ULC-S102. This standard should be used to measure and describe the properties of materials, products, or assemblies in response to heat and flame under controlled laboratory conditions and should not be used to describe or appraise the fire hazard or fire risk of materials, products, or assemblies under actual fire conditions. However, results of this test may be used as elements of a fire risk assessment which takes into account all of the factors which are pertinent to an assessment of the fire hazard of a particular end use.

Sound Absorption Coefficient, ASTM C423—Type “A” Mounting2


Product


Thickness

Octave Band Center Frequencies, Hz

125

250

500

1000

2000

4000

NRC

SAA

RA-261.00.110.300.590.770.850.860.650.63
RA-262.00.260.771.091.060.961.000.950.97
RA-251.00.120.360.750.910.970.910.750.75
RA-241.00.110.380.710.900.950.910.750.74
RA-242.00.150.771.111.081.001.031.000.99
RA-231.00.110.380.800.950.990.950.800.79
RA-232.00.130.771.121.091.041.041.001.00

RA-22

2.0

0.20

0.87

1.19

1.11

1.06

1.05

1.0

1.04

2. Nominal samples were measured in accordance with ASTM C423. These measured absorption coefficients were adjusted to values representative of the product with mean specification properties. While these values are an accurate representation of our product, they are for design approximations only. Production, testing, and application variabilities will alter results. Specific designs should be evaluated in end-use configurations.

Thermal Conductivity — “k”, ASTM C177


Type

Nominal "K"

Density3

BTU · IN/HR · FT2 · °F 2 75° (23°C) MEAn

W/MK

(PCF)

(KG/M3)

RA-260.2600.0370.9515.2
RA-250.2500.0361.0817.3
RA-240.2400.0351.3421.5
RA-230.2310.0331.6626.6

RA-22

0.223

0.032

2.27

36.4

3. Density value is nominal. Product control is on thermal conductivity

Availability
RA Insulation is available in both batt and roll form and 1/4” increments in the following thicknesses.


Product

Thickness

Rolls

Batts

RA-263/4”–5”Not Available
RA-253/4”–5”Not Available
RA-243/4”–4”3/4”–4 1/2”
RA-23

3/4”–3”

3/4”–3 1/2”

RA-22

3/4" –1 1/2"

3/4" –2 1/2"

Applications

Contact Us

Even though we’re a global company, we’re always ready to answer your questions. Call to speak with an Owens Corning representative.